System assembly, construction and connection
AC500-XC > System data AC500-XC
Parameter
Temperature
Humidity
Air pressure
Immunity to corrosive gases
Immunity to salt mist
1024
The creepage distances and clearances meet the requirements of the over-
voltage category II, pollution degree 2.
Operating
Storage / Transport
3ADR010278, 3, en_US
Value
-40 °C...+70 °C
-40 °C...-30 °C: Proper start-up of system;
technical data not guaranteed
-40 °C...0 °C: Due to the LCD technology, the
display might respond very slowly.
-40 °C...+40 °C: Vertical mounting of modules
possible, output load limited to 50 % per group
+60 °C...+70 °C with the following deratings:
System is limited to max. 2 communication
modules per terminal base
Applications certified for cULus up to +60
°C
Digital inputs: maximum number of simul-
taneously switched on input channels
limited to 75 % per group (e.g. 8 channels
=> 6 channels)
Digital outputs: output current maximum
value (all channels together) limited to 75
% per group (e.g. 8 A => 6 A)
Analog outputs only if configured as
voltage output: maximum total output
current per group is limited to 75 %
(e.g. 40 mA => 30 mA)
Analog outputs only if configured
as current output: maximum number
of simultaneously used output chan-
nels limited to 75 % per group
(e.g. 4 channels => 3 channels)
-40 °C...+85 °C
Operating / Storage: 100 % r. H. with conden-
sation
Operating:
-1000 m....4000 m (1080 hPa...620 hPa)
> 2000 m (< 795 hPa):
max. operating temperature must be
reduced by 10 K (e.g. 70 °C to 60°C)
I/O module relay contacts must be oper-
ated with 24 V nominal only
Operating: Yes, according to:
ISA S71.04.1985 Harsh group A, G3/GX
IEC 60721-3-3 3C2 / 3C3
Operating: Yes, horizontal mounting only,
according to IEC 60068-2-52 severity level: 1
2022/01/31