ABB AC500 V3 Hardware Manual page 477

Hide thumbs Also See for AC500 V3:
Table of Contents

Advertisement

E1...E4
d1
Class
Comp
Byte 6
-
Bit 6...7
Class
Interface
1
)
4
14
11 / 12
4
14
11 / 12
Remarks:
1
)
2
)
3
)
4
)
State LEDs
During the power ON procedure, the module initializes automatically. All LEDs (except the
channel LEDs) are ON during this time.
States of the LEDs (see also section Diagnosis LEDs in the S500 system data):
2022/01/31
d2
d3
Dev
Mod
Byte 3
Byte 4
Device
Module
2
3
)
)
1...10
1
ADR
1...10
1...10
1
ADR
1...10
In AC500, the following interface identifier applies:
14 = I/O bus, 11 = COM1 (e.g. CS31 bus), 12 = COM2.
The FBP diagnosis block does not contain this identifier.
With "Device" the following allocation applies:
31 = module itself, 1...10 expansion module 1...10, ADR = hardware
address (e.g. of the DC551)
With "Module" the following allocation applies dependent of the master:
Module error: I/O bus or FBP: 31 = module itself; COM1/COM2: 1...10 =
expansion 1...10
Channel error: I/O bus or FBP = module type (1 = AI); COM1/COM2:
1...10 = expansion 1...10
In case of module errors, with channel "31 = Module itself" is output.
3ADR010278, 3, en_US
d4
Identifier
000...063
Ch
Err
Byte 5
Byte 6
Bit 0...5
Channel
Error
identifier
4
)
0...7
2
0...7
11
Device specifications
I/O modules > Analog I/O modules
AC500
<− Display in
display
PS501
PLC
browser
FBP diag-
nosis
block
Error message
Invalid measured value
of the channel caused
by overly high voltage
difference
Output voltage 10 V
faulty
Remedy
Check
voltage dif-
ference;
install
equalizing
conductors
if neces-
sary
Check
output load
477