Parameter
Process supply voltage UP
Connections
Rated value
Current consumption
Inrush current (at power-up)
Max. ripple
Protection against reversed voltage
Protection fuse for UP
Current consumption from 24 V DC power
supply at the terminals UP/L+ and ZP/M of
the CPU/communication interface module
Galvanic isolation
Isolated groups
Surge-voltage (max.)
Max. power dissipation within the module
Weight
Mounting position
Cooling
Technical data of the analog inputs
Parameter
Number of channels per module
Distribution of channels into groups
Resolution
Connection of the signals O0+ and
O1+
Connection of the signals I0- and I1-
Connection of the signals I0+ and I1+
Input type
2022/01/31
NOTICE!
Attention:
All I/O channels (digital and analog) are protected against reverse polarity,
reverse supply, short circuit and continuous overvoltage up to 30 V DC.
RTD
Resistance
3ADR010278, 3, en_US
Value
Terminal 19 for UP (+24 V DC) and terminal 20
for ZP (0 V)
24 V DC
0.04 A
0.05 A
2
s
5 %
Yes
Recommended
Ca. 5 mA
Yes, between the input group and the rest of the
module
1 (2 channels per group)
35 V DC for 0.5 s
1.1 W
Ca. 120 g
Horizontal or vertical
The natural convection cooling must not be
hindered by cable ducts or other parts in the
switchgear cabinet.
Value
2 configurable RTD (resistance temperature detector)
inputs
1 (2 channels per group)
0.1 °C / 0.1 °F
15 bits + sign
Terminals 10 and 13
Terminals 11 and 14
Terminals 12 and 15
Module ground referenced RTD for 2-wire and 3-wire
resistance temperature detectors
Device specifications
I/O modules > Analog I/O modules