ABB AC500 V3 Hardware Manual page 167

Hide thumbs Also See for AC500 V3:
Table of Contents

Advertisement

Parameter
Input signal range
Signal 0
Undefined signal
Signal 1
Input current per channel
Input voltage 24 V
Input voltage 5 V
Input voltage 14 V
Input voltage 15 V
Input voltage 27 V
Input voltage 30 V
Max. permissible leakage current (at
2-wire proximity switches)
Input delay (0->1 or 1->0)
Input data length
Max. cable length
Shielded
Unshielded
1
) When inputs are used with 24 V AC, external surge limiting filters are required.
Ordering data
Part no.
1TNE 968 902 R2101 DI561, digital input module, 8 DI,
1TNE 968 901 R3101 Terminal block TA563-9, 9 pins, screw
1TNE 968 901 R3103 Terminal block TA564-9, 9 pins, screw
1TNE 968 901 R3105 Terminal block TA565-9, 9 pins, spring
1.6.1.1.4
DI562 - Digital input module
16 digital inputs 24 V DC / 24 V AC (I0 to I15) in 2 groups
Group-wise galvanically isolated
2022/01/31
Description
24 V DC / 24 V AC
front, cable side, 6 pieces per unit
front, cable front, 6 pieces per unit
front, cable front, 6 pieces per unit
*) Modules in lifecycle Classic are available from stock but not recommended
for planning and commissioning of new installations.
3ADR010278, 3, en_US
Value
-24 V DC
+24 V DC
-5 V...+3 V
-3 V...+5 V
-15 V...-5 V
+5 V...+15 V
-30 V...-15 V
+15 V...+30 V
Typ. 5 mA
Typ. 1 mA
> 2.5 mA
< 8 mA
1 mA
Typ. 8 ms
1 byte
500 m
300 m
Device specifications
I/O modules > Digital I/O modules
24 V AC 50/60 Hz
0 V AC...5 V AC
5 V AC...14 V AC
14 V AC...27 V AC
Typ. 5 mA r.m.s.
Typ. 1 mA r.m.s.
Typ. 2.7 mA r.m.s.
Typ. 5.5 mA r.m.s.
Typ. 1 mA r.m.s.
Product life cycle phase *)
Active
Active
Active
Active
167

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ac500-eco v3Ac500-xc v3

Table of Contents