The module provides several diagnosis functions
on page 173.
The digital inputs can be used as source inputs or as sink inputs.
The following figure shows the connection of the digital input module DI562:
24 V
DC/AC
Connection of DI562 - sink inputs
2022/01/31
NOTICE!
Risk of damaging the PLC modules!
Overvoltages and short circuits might damage the PLC modules.
Make sure that all voltage sources (supply voltage and process supply
voltage) are switched off before you begin with operations on the system.
Never connect any voltages or signals to reserved terminals (marked with
---). Reserved terminals may carry internal voltages.
NOTICE!
Risk of malfunctions in the plant!
A ground fault, e. g. caused by a damaged cable insulation, can bridge switches
accidentally.
Use sink inputs when possible or make sure that, in case of error, there will be
no risks to persons or plant.
1
C0..7
2
I0
3 I1
4 I2
+ / ~
5 I3
– / ~
6 I4
7 I5
8 I6
9 I7
10
C8..15
11
I8
12 I9
13 I10
14 I11
15 I12
16 I13
17 I14
18 I15
19 ---
20 ---
3ADR010278, 3, en_US
I/O modules > Digital I/O modules
Ä Chapter 1.6.1.1.4.6 "Diagnosis"
+ / ~
24 V
DC/AC
– / ~
Connection of DI562 - source inputs
Device specifications
1
C0..7
2
I0
3 I1
4 I2
5 I3
6 I4
7 I5
8 I6
9 I7
10
C8..15
11
I8
12 I9
13 I10
14 I11
15 I12
16 I13
17 I14
18 I15
19 ---
20 ---
171