ABB AC500 V3 Hardware Manual page 325

Hide thumbs Also See for AC500 V3:
Table of Contents

Advertisement

LED
Technical data
The system data of AC500 and S500
applicable to the standard version.
The system data of AC500-XC
applicable to the XC version.
Only additional details are therefore documented below.
The technical data are also applicable to the XC version.
Parameter
Process supply voltage UP, UP3 and UP4
Connections
Rated value
Max. ripple
Protection against reversed voltage
Rated protection fuse on UP, UP3 and
UP4
Galvanic isolation
Current consumption
From 24 V DC power supply at the ter-
minals UP/L+ and ZP/M of the CPU/com-
munication interface module
From UP at normal operation / with out-
puts
From UP3 or UP4 at normal operation /
with outputs
Inrush current from UP (at power up)
2022/01/31
State
CH-ERR3
Channel
Error, error
CH-ERR4
messages in
groups (dig-
ital outputs
combined
into the
groups 3, 4)
) Module Error Red
1
CH-ERR
1
) All of the LEDs CH-ERR3 to CH-ERR4 light up together
2
) The state of the LEDs corresponds to the logic state of the output. In case
of missing or low process supply voltage UP3 or UP4, the signal on the output
terminal is off even though the LED is on.
Ä Chapter 2.7.1 "System data AC500-XC" on page 1023 are
3ADR010278, 3, en_US
Color
LED = OFF
Red
No error or
process
Red
supply
voltage is
missing
--
Ä Chapter 2.6.1 "System data AC500" on page 971 are
Value
Terminals 1.8 and 2.8 for +24 V (UP) as well as
1.9 and 2.9 0 V (ZP)
Terminals 3.8 for +24 V (UP3) as well as 3.9 for
0 V (ZP3)
Terminals 4.8 for +24 V (UP4) as well as 4.9 for
0 V (ZP4)
24 V DC
5 %
Yes
10 A fast (for each process supply voltage)
Yes, per module and per output channel groups
Ca. 2 mA
Ca. 20 mA + 1.5 mA per output
Ca. 0.01 A + max. 2 A per output
0.015 A²s
Device specifications
I/O modules > Digital I/O modules
LED = ON
LED flashes
Severe error
Error on in the
within the cor-
corresponding
responding
group
group
Internal error
--
325

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ac500-eco v3Ac500-xc v3

Table of Contents