ABB AC500 V3 Hardware Manual page 695

Hide thumbs Also See for AC500 V3:
Table of Contents

Advertisement

Group parameters of the cam switch
Name
numOfUsed-
Cams
resolution
zeroShift
EncoderBitReso-
lution
Reserve
1
) The parameter numOfUsedCams defines the interrupt cycle time (Therefore, it takes effect to
the accuracy of the track) and the behavior of the module if the DC information is lost.
Parameter setting
for numOfUsed-
Cams
0
1...8
9...16
17...32
128
129...136
137...144
145...170
2
) The parameter resolution defines the angle resolution of the track. The value gives the
number of increments related to 360°; e. g. the value 36,000 corresponds to an angle resolution
of 0.01°.
3
) The parameter zeroShift defines the zero shift. With it the encoder can be adjusted to the
mounting position. The value of zeroShift is set in encoder-increments. It is not assigned to the
parameter resolution of the cam switch.
4
) The parameter EncoderBitResolution defines the resolution of the used encoder (in bits), e. g.
with the default setting 18 bits the encoder has 196,608 divisions.
2022/01/31
Value
0 ... 32
1
)
128...160
0 ... 2
2
)
-1
3
0 ... 2
)
-1
8 ... 32
4
)
-
Number of cams
used
0
1...8
9...16
17...32
0
1...8
9...16
17...32
3ADR010278, 3, en_US
Communication interface modules (S500) > EtherCAT
Internal value
Internal value,
type
0 ... 32
WORD
218...160
0 ... 2
DWORD
-1
0 ... 2
DWORD
-1
8 ... 32
WORD
-
WORD
Interrupt cycle time
50 µs
80 µs
100 µs
200 µs
50 µs
80 µs
100 µs
200 µs
Device specifications
Default
0
36000
0
18
-
Behavior if DC infor-
mation is lost
Module changes
to "safe-operational"
state; the outputs are
activated trough the
user program
Module keeps in
"operational" state;
the outputs are acti-
vated trough the user
program
Module keeps in
"operational" state;
the cam switch out-
puts are activated
according to an inter-
polated timing infor-
mation
695

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ac500-eco v3Ac500-xc v3