Mechanical Dimensions - ABB AC500 V3 Hardware Manual

Hide thumbs Also See for AC500 V3:
Table of Contents

Advertisement

2.5.2 Mechanical dimensions

2.5.2.1
Switchgear cabinet assembly (indoor use)
PLC enclosure
To protect PLCs against:
unauthorized access,
dusting and pollution,
moisture and wetness and
mechanical damage,
switchgear cabinet IP54 for common dry factory floor environment is suitable.
Maintain spacing from:
enclosure walls
wireways
adjacent equipment
Allow a minimum of 20 mm clearance on all sides. This provides ventilation and galvanic
isolation.
It is recommended to mount the modules on an grounded mounting plate, or an grounded DIN
rail, independent of the mounting location.
Fig. 176: Installation of AC500-eCo V3 CPU/S500 modules in a switchgear cabinet
1
Cable duct
2
Distance from cable duct ≥20 mm
3
Mounting plate, grounded
2022/01/31
Information on EMC-conforming assembly and construction is provided within
the overall functions section
construction" on page 918.
3ADR010278, 3, en_US
System assembly, construction and connection
Ä Chapter 2.4.4 "EMC-conforming assembly and
AC500-eCo > Mechanical dimensions