Parameter
Output current limitation
Resistance to feedback against 24 V DC
Connection of 2 outputs in parallel
Max. cable length *)
Shielded
Unshielded
*) For fast inputs and fast outputs including PTO and PWM, a shielded cable must be used and
the max. cable length is 50 m.
Table 16: PM5032-T-ETH, PM5072-T-2ETH and PM5072-T-2ETHW
Parameter
Number of channels per module
Distribution of the channels into groups
Galvanic isolation
Connection of the channels O0 to O7
Common power supply voltage
Reference potential for the channels O0 to O7
Indication of the output signals
Way of operation
Min. output voltage at signal 1
Output delay (max. at rated load)
0 to 1
1 to 0
Rated protection fuse (per group)
Output current
Rated current per channel (max.)
Rated current per group (max.)
Rated current (all channels together, max.)
Max. leakage current with signal 0
Demagnetization when inductive loads are
switched off
Switching Frequencies
With inductive loads
Short-circuit-proof / Overload-proof
Overload message
Output current limitation
Resistance to feedback against 24 V DC
Connection of 2 outputs in parallel
Max. cable length *)
2022/01/31
Value
No
No
Not possible
On request
On request
Value
8
1 group of 8 channels
Yes, per group
Terminals 14 to 21
Terminals 24 (+24 V DC, signal name UP)
Terminal 25 (0 V DC, negative pole of the
process voltage, signal name ZP)
1 yellow LED per channel; the LED is on
when the output signal is high (signal 1)
Non-latching type
UP - 0.1 V
On request
On request
On request
0.5 A at UP 24 V DC (resistance, general
use and pilot duty)
4 A
4 A
0.5 mA
Must be performed externally according to
driven load specification
On request
No
No
No
No
Not possible
3ADR010278, 3, en_US
Device specifications
Processor modules > AC500-eCo
39

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ac500-eco v3Ac500-xc v3

Table of Contents