ABB AC500 V3 Hardware Manual page 338

Hide thumbs Also See for AC500 V3:
Table of Contents

Advertisement

Device specifications
I/O modules > Digital I/O modules
Parameter
Output switching capacity (XC ver-
sion above 60 °C)
Lifetime (cycles)
Spark suppression with inductive AC
load
Demagnetization with inductive DC
load
Switching frequency
Max. cable length
Technical data of the fast counter
Parameter
Used inputs
Used outputs
Counting frequency
Detailed description
Ordering data
Part no.
1SAP 245 200 R0001 DX522, digital input/output module,
1SAP 445 200 R0001 DX522-XC, digital input/output
338
With resistive load
With inductive load
With lamp load
Shielded
Unshielded
The fast counter of the module does not work if the module is connected to a
FBP interface module
CS31 bus module
CANopen communication interface module
Description
8 DI, 24 V DC, 8 DO relays
module, 8 DI, 24 V DC, 8 DO relays,
XC version
3ADR010278, 3, en_US
Value
On request
Mechanical: 300 000;
Under load: 300 000 (24 V DC at 2 A), 200 000 (120 V
AC at 2 A), 100 000 (230 V AC at 3 A)
Must be performed externally according to driven load
specifications
A free-wheeling diode must be circuited in parallel to
the inductive load
Max. 10 Hz
Max. 2 Hz
On request
1000 m
600 m
Value
I0 / I1
None
50 kHz max.
See
Product life cycle phase *)
Active
Active
2022/01/31

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ac500-eco v3Ac500-xc v3

Table of Contents