Fig. 107: Connection of active-type sensors (voltage) with no galvanically isolated power supply
to the analog inputs
Voltage
Voltage
For the measuring ranges that can be configured, plese refer to the sections Measuring Ranges
Ä Chapter 1.7.2.2.10 "Measuring ranges" on page 650 and Parameterization Ä Chapter
1.7.2.2.7 "Parameterization" on page 640.
To avoid error messages, configure unused analog input channels as "unused".
Connection of passive-type analog sensors (Current) to the analog inputs
The following figure shows the connection of passive-type analog sensors (current) to the
analog input AI0. Proceed with the analog inputs AI1 to AI3 in the same way.
2022/01/31
-10 ... +10 V
0 ... +10 V
+
24 V DC
-
NOTICE!
Risk of faulty measurements!
The negative pole/ground potential at the sensors must not have too large a
potential difference with respect to ZP (max. ± 1 V within the full signal range).
Make sure that the potential difference never exceeds ± 1 V.
0...10 V
-10 V...+10 V
3ADR010278, 3, en_US
Communication interface modules (S500) > CANopen
2.0
AI0+
2.1
AI1+
2.2
AI2+
2.3
AI3+
2.4
AI-
2.5
AO0+
2.6
AO1+
2.7
AO-
2.8
UP
2.9
ZP
1 channel used
1 channel used
Device specifications