ABB AC500 V3 Hardware Manual page 547

Hide thumbs Also See for AC500 V3:
Table of Contents

Advertisement

Parameter
Unused current inputs
Overvoltage protection
Technical data of the analog inputs, if used as digital Inputs
Parameter
Number of channels per module
Distribution of channels into groups
Connections of the channels I0+ to I7+
Reference potential for the inputs
Input signal delay
Indication of the input signals
Input signal voltage
Input current per channel
Input resistance
Technical data of the analog outputs
Parameter
Number of channels per module
Distribution of channels into groups
Channels O0-...O7-
Channels O0+...O7+
Output type
Galvanic isolation
Configurability
Output resistance (load), as current output
Output loadability, as voltage output
Indication of the output signals
Resolution
2022/01/31
Signal 0
Undefined signal
Signal 1
Input voltage +24 V
Input voltage +5 V
Input voltage +15 V
Input voltage +30 V
3ADR010278, 3, en_US
I/O modules > Analog I/O modules
Value
Have a low resistance, can be left open-circuited
Yes
Value
Max. 8
1 group of 8 channels
Terminals 2.0 to 2.7
Terminals 1.9, 2.9, 3.9 and 4.9 (ZP)
Typ. 8 ms, configurable from 0.1 to 32 ms
1 LED per channel
24 V DC
-30 V...+5 V
+5 V...+13 V
+13 V...+30 V
Typ. 7 mA
Typ. 1.4 mA
Typ. 4.3 mA
< 9 mA
Ca. 3.5 kW
Value
8, all channels for voltage, the first 4 channels
also for current
1 group of 8 channels
Terminals 3.0...3.7
Terminals 4.0...4.7
Bipolar with voltage, unipolar with current
Against internal supply and other modules
-10 V...+10 V, 0 mA...20 mA, 4 mA...20 mA
(each output can be configured individually),
current outputs only channels 0...3
0 W...500 W
Max. ±10 mA
One LED per channel
12 bits (+ sign)
Device specifications
547

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ac500-eco v3Ac500-xc v3

Table of Contents