I/O Modules; Digital I/O Modules - ABB AC500 V3 Hardware Manual

Hide thumbs Also See for AC500 V3:
Table of Contents

Advertisement

Device specifications
I/O modules > Digital I/O modules

1.6 I/O modules

1.6.1 Digital I/O modules

1.6.1.1
S500-eCo
1.6.1.1.1
DC561 - Digital input/output module
16 configurable digital inputs/outputs 24 V DC,
Connection via Interfast
Module-wise galvanically isolated
142
Hot swap
System requirements for hot swapping of I/O modules:
Types of terminal units that support hot swapping of I/O modules have the
appendix TU5xx-H.
I/O modules as of index F0.
The following I/O bus masters support hot swapping of attached I/O modules:
Communication interface modules CI5xx as of index F0.
Processor modules PM56xx-2ETH with firmware version as of V3.2.0.
NOTICE!
Risk of damage to I/O modules!
Hot swapping is only allowed for I/O modules.
Processor modules and communication interface modules must not be removed
or inserted during operation.
Conditions for hot swapping
Digital outputs are not under load.
Input/output voltages above safety extra low voltage/
protective extra low voltages (SELV/PELV) are switched off.
Modules are completely plugged on the terminal unit with both snap fit
engaged before switching on loads or input/output voltage.
Hot swap
Further information about hot swap: .
3ADR010278, 3, en_US
2022/01/31

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ac500-eco v3Ac500-xc v3

Table of Contents