Device specifications
I/O modules > Digital I/O modules
Internal data exchange
Digital inputs (bytes)
Digital outputs (bytes)
Counter input data (words)
Counter output data (words)
I/O configuration
The module itself does not store configuration data. It receives its parameterization data from
the master device of the I/O bus (CPU or communication interface module) during power-up of
the system.
Hence, replacing I/O modules is possible without any re-parameterization via software.
Parameterization
Firmware version
Firmware version > V2.0.0
The parameter data directly influences the functionality of modules.
For non-standard applications, it is necessary to adapt the parameters to your system configura-
tion.
Module: Module slot address: Y = 1...10
Name
Module ID Internal
Ignore
module
2
)
Parameter
length
Check
supply
284
Without the fast counter
3
3
0
0
If the external power supply voltage via UP/ZP terminals fails, the I/O module
loses its configuration data. The whole station has to be switched off and on
again to re-configure the module.
Value
Internal
value
1215
1
)
No
0
Yes
1
Internal
9
Off
0
on
1
3ADR010278, 3, en_US
Configuration
The arrangement of the parameter data is per-
formed by Control Builder Plus/ Automation
Builder software.
Internal
Default
value,
type
Word
1215
0x04BF
Byte
No
0x00
Byte
9-CPU
8-FBP
Byte
On
0x01
With the fast counter (only
with AC500)
5
5
4
8
Min.
Max.
0
65535
0
255
0
1
EDS Slot/
Index
0x0Y01
Not for
FBP
0x0Y02
0x=Y03
2022/01/31