ABB AC500 V3 Hardware Manual page 36

Hide thumbs Also See for AC500 V3:
Table of Contents

Advertisement

Device specifications
Processor modules > AC500-eCo
Parameter
Indication of the input signals
Input type according to EN 61131-2
Input signal voltage
Ripple with signal 0
Ripple with signal 1
Input current per channel
Max. permissible leakage current (at 2-wire prox-
imity switches)
Input delay (0->1 or 1->0)
Max. cable length *)
*) For fast inputs and fast outputs including PTO and PWM, a shielded cable must be used and
the max. cable length is 50 m.
Technical data of the fast counter inputs
The AC500-eCo V3 processor modules with onboard I/Os provide some special functionality on
the digital inputs or digital outputs. Fast counter, encoder inputs, interrupt inputs or PWM/PTO
outputs are available depending on the device used.
The fast counter functionality can be activated within the onboard I/O configuration.
The fast counter can work in pulse/direction mode or A/B track counter mode.
The pulse/direction counter detects the rising edge of the counter input. It will increase or
decrease the count value (depending on the direction input) at every rising edge.
The A/B track counter is used to count the signal from an encoder.
The counter can count with quad phases. In the following the behavior of the A/B track counter
is described.
36
Signal 0
Undefined signal
Signal 1
Input voltage +24 V
Input voltage +5 V
Input voltage +15 V
Input voltage +30 V
Shielded
Unshielded
For AC500 devices the function "fast counter" is available in S500 I/O modules
as of firmware version V1.3.
For AC500-eCo V3 devices the function "fast counter" is available in onboard
I/Os of PM50xx.
3ADR010278, 3, en_US
Value
1 yellow LED per channel; the LED is ON
when the input signal is high (signal 1)
and the module's logic is in operation
Type 1 source
Type 1 sink
-24 V DC
+24 V DC
-5 V...+3 V
-3 V...+5 V
-15 V...- 5 V
+5 V...+15 V
-30 V...-15 V
+15 V...+30 V
Within -5 V...+3 V
Within -3 V...+5 V
Within -30 V...-15 V Within +15 V...+30
V
Typ. 4.6 mA
Typ. 0.8 mA
> 2.5 mA
< 8 mA
1 mA
On request
On request
On request
2022/01/31