ABB AC500 V3 Hardware Manual page 972

Hide thumbs Also See for AC500 V3:
Table of Contents

Advertisement

System assembly, construction and connection
AC500 (Standard) > System data AC500
Parameter
Temperature
Humidity
Air pressure
Ingress protection
2.6.1.2
Creepage distances and clearances
The creepage distances and clearances meet the requirements of the overvoltage category II,
pollution degree 2.
2.6.1.3
Insulation test voltages, routine test
According to EN
Parameter
61131-2
230 V circuits against other
circuitry
120 V circuits against other
circuitry
120 V...240 V circuits against
other circuitry
24 V circuits (supply, 24 V
inputs/outputs, analog inputs/
outputs), if they are galvani-
cally isolated against other cir-
cuitry
972
NOTICE!
Improper voltage level or frequency range which cause damage of AC inputs:
AC voltage above 264 V
Frenquency below 47 Hz or above 62.4 Hz
NOTICE!
Improper connection leads cause overtemperature on terminals.
PLC modules may be destroyed by using wrong cable type, wire size and cable
temperature classification.
Operating
Storage
Transport
Operating
Storage
3ADR010278, 3, en_US
Value
0 °C...+60 °C: Horizontal mounting of modules.
0 °C...+40 °C: Vertical mounting of modules.
Output load reduced to 50 % per group.
-40 °C...+70 °C
-40 °C...+70 °C
Max. 95 %, without condensation
> 800 hPa / < 2000 m
> 660 hPa / < 3500 m
IP20
Value
2500 V
1500 V
2500 V
500 V
1.2/50 µs
1.2/50 µs
1.2/50 µs
1.2/50 µs
2022/01/31