Device specifications
Processor modules > AC500-eCo
Parameter
Shielded
Unshielded
*) For fast inputs and fast outputs including PTO and PWM, a shielded cable must be used and
the max. cable length is 50 m.
Technical data of the digital relay outputs
Table 17: PM5012-R-ETH
Parameter
Number of channels per module
Distribution of the channels into groups
Galvanic isolation
Connection of the channels NO0 to NO1
Connection of the channels NO2 to NO3
Reference potential R0..1 for the channels NO0
to NO1
Reference potential R2..3 for the channels NO2
to NO3
Relay output voltage
Rated value
Range
Indication of the output signals
Way of operation
Output delay
0 to 1
1 to 0
Rated protection fuse
Output current
Rated current per channel (max.)
Rated current per group (max.)
Rated current (all channels together, max.)
Demagnetization when inductive loads are
switched off
Spark suppression with inductive AC loads
Switching frequencies
40
Value
On request
On request
Value
4 normally-open relay outputs
2 groups for 2 channels
Yes, per group
Terminals 8 to 9
Terminals 11 to 12
Terminal 10
Terminal 13
24 V DC or
100 V AC...240 V AC
50 Hz/60 Hz
5 V DC...30 V DC
or
5 V AC...250 V AC
1 yellow LED per channel; the LED is on
when the output signal is high (signal 1)
Non-latching type
Typ. 10 ms
Typ. 10 ms
On request
2.0 A (24 V DC resistance and general use,
100 V AC...240 V AC, resistance, general
use and pilot duty)
6 A
12 A
External demagnetization measures must be
implemented when switching inductive loads.
Must be performed externally according to
driven load specification
3ADR010278, 3, en_US
2022/01/31