Device specifications
I/O modules > Digital/Analog I/O modules
Parameter
Settling time for full range change (resistive
load, output signal within specified tolerance)
Conversion error of the analog values caused
by non-linearity, adjustment error at factory
and resolution within the normal range
Relationship between output signal and hex
code
Unused outputs
Ordering data
Part no.
1SAP 250 000 R0001 AX522, analog input/output module,
1SAP 450 000 R0001 AX522-XC, analog input/output
1.6.3 Digital/Analog I/O modules
1.6.3.1
S500
1.6.3.1.1
DA501 - Digital/Analog input/output module
●
16 digital inputs 24 V DC
●
8 configurable digital inputs/outputs 24 V DC, 0.5 A max.
●
4 analog inputs, voltage, current and RTD.
Resolution 12 bits plus sign
●
2 analog outputs, voltage and current
Resolution 12 bits plus sign
●
Fast counter
●
Module-wise galvanically isolated
●
XC version for use in extreme ambient conditions available
548
Description
8 AI, 8 AO, U/I/Pt100, 12 bits + sign,
2-wires
module, 8 AI, 8 AO, U/I/Pt100,
12 bits + sign, 2-wires, XC version
*) Modules in lifecycle Classic are available from stock but not recommended
for planning and commissioning of new installations.
3ADR010278, 3, en_US
Value
Typ. 5 ms
Typ.
±0.5 % of full scale
at 25 °C
Max.
±1 % of full scale (all ranges)
at 0 °C...60 °C or EMC disturbance
Ä Chapter 1.6.2.2.6.9.3 "Output
See table,
ranges voltage and current" on page 544
Can be left open-circuited
Product life cycle phase *)
Active
Active
2022/01/31