Device specifications
Communication modules (AC500 standard) > PROFINET
LED
1.4.5.1.5
Technical data
The system data of AC500 and S500
applicable to the standard version.
The system data of AC500-XC
applicable to the XC version.
Only additional details are therefore documented below.
The technical data are also applicable to the XC version.
Parameter
Protocol
Bus connection
Switch
Technology
Transfer rate
Transfer method
Ethernet
Bus length (segment length max.)
Indicators
Usable terminal bases
Supported alarm types
Alarm processing
Current consumption from 24 V DC power
supply at the terminal base of the CPU
Internal supply
Weight
120
Color
PNIO2 LED "RX/TX" Yellow
Ä Chapter 2.7.1 "System data AC500-XC" on page 1023 are
3ADR010278, 3, en_US
State
Description
Off
No Ethernet connection
On
---
Blinking
PROFINET device sends/receives
frames
Off
---
Ä Chapter 2.6.1 "System data AC500" on page 971 are
Value
PROFINET IO RT
2 RJ45 (PNIO1 and PNIO2), with integrated 2-
port switch
Integrated
Hilscher NETX 100
100 Mbit/s (full-duplex)
According to Ethernet II, IEEE 802.3
100 base-TX, internal switch, 2x RJ45 socket
100 m
5 LEDs
All TB5xx
All TB56xx (not TB5600)
"TB56xx for AC500 V3 products" on page 4
Process alarm, diagnostic alarm, return of Sub-
Module, plug alarm, pull alarm
Requires handling in application program
Typ. 85 mA
Via the communication module interface of the
terminal base
Ca. 170 g
Ä Chapter 1.2.1