ABB AC500 V3 Hardware Manual page 354

Hide thumbs Also See for AC500 V3:
Table of Contents

Advertisement

Device specifications
I/O modules > Analog I/O modules
The following figures are an example of the connection of analog sensors (voltage) to the input
I0 of the analog input module AI561. Proceed with the inputs I1 to I3 in the same way.
U
IN
24 VDC
Connection of active-type analog sensors
(voltage)
The following figures are an example of the connection of analog sensors (current) to the input
I0 of the analog input module AI561. Proceed with the inputs I1 to I3 in the same way.
U
IN
Connection of active-type analog sensors
(current)
The meaning of the LEDs is described in the Displays section
LEDs" on page 357.
I/O configuration
The analog input module AI561 does not store configuration data itself.
354
CAUTION!
Risk of damaging the analog input!
The 250 Ω input resistor can be damaged by overcurrent.
Make sure that the current through the resistor never exceeds 30 mA.
+
-
-2.5 ... +2.5 V
-5 ... +5 V
0 ... 5 V
0 ... 10 V
+
-
+
4 ... 20 mA
0 ... 20 mA
+
24 VDC
3ADR010278, 3, en_US
250 Ω
R0
I0+
I0−
1
R0
2
I0+
3 I0-
18 SG
19 L+
20 M
-
24 VDC
Connection of passive-type analog sensors
(voltage)
1
R0
2
I0+
3 I0–
18 SG
19 L+
24 VDC
20 M
Connection of passive-type analog sensors
(current)
1
R0
2
I0+
3 I0-
-2.5 ... +2.5 V
-5 ... +5 V
0 ... 5 V
0 ... 10 V
18 SG
19 L+
20 M
1
R0
4 ... 20 mA
2
I0+
+
3 I0–
18 SG
+
19 L+
20 M
Ä Chapter 1.6.2.1.1.7 "State
2022/01/31

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ac500-eco v3Ac500-xc v3

Table of Contents