Internal data exchange
Digital inputs (bytes)
Digital outputs (bytes)
I/O configuration
The module itself does not store configuration data. It receives its parameterization data from
the master device of the I/O bus (CPU or communication interface module) during power-up of
the system.
Hence, replacing I/O modules is possible without any re-parameterization via software.
Parameterization
The arrangement of the parameter data is performed with Automation Builder software, versions
≥ 1.2.3.
The parameter data directly influences the functionality of modules.
For non-standard applications, it is necessary to adapt the parameters to your system configura-
tion.
Module: Module slot address: Y = 1...7
Name
Module ID Internal
Ignore
module
2
)
Parameter
length
Check
supply
Reserve
Behaviour
of outputs
at com-
munica-
tion errors
2022/01/31
If the external power supply voltage via UP/ZP terminals fails, the I/O module
loses its configuration data. The whole station has to be switched off and on
again to re-configure the module.
Value
Internal
value
1105
1
)
No
0
Yes
1
Internal
6
Off
0
on
1
0...255
0...0xff
Off
0
Last value
1+(n*5)
Substitute
2+(n*5),
value
n £ 2
3ADR010278, 3, en_US
0
1
Internal
Default
value,
type
WORD
1105
0x0451
BYTE
No
0x00
BYTE
6-CPU
6-FBP
BYTE
On
0x01
BYTE
On
0x01
BYTE
Off
0x00
Device specifications
I/O modules > Digital I/O modules
Min.
Max.
0
65535
0
6
0
1
0
1
0
2
Max.
0x0Y01
not for
FBP
0x0Y02
0x0Y03
0x0Y04
0x0Y05
323