Device specifications
I/O modules > Digital/Analog I/O modules
Range
Measured value too
low
Underflow
Output ranges voltage and current
Range
Overflow
Value too high 11.7589 V
Normal range 10.0000 V
Value too low
Underflow
The represented resolution corresponds to 16 bits.
Technical data
Technical data of the module
The system data of AC500 and S500
applicable to the standard version.
The system data of AC500-XC
applicable to the XC version.
Only additional details are therefore documented below.
The technical data are also applicable to the XC version.
608
Pt100 /
Pt100 /
Pt1000
Pt1000
-50...70 °C
-50...400 °C
-50.1 °C
-50.1 °C
:
:
-60.0 °C
-60.0 °C
< -60.0 °C
< -60.0 °C
-10...+10 V
0...20 mA
0 V
0 mA
23.5178 mA
:
:
10.0004 V
20.0007 mA
20.0000 mA
:
:
0.0004 V
0.0007 mA
0.0000 V
0.0000 mA
-0.0004 V
0 mA
:
:
-10.0000 V
0 mA
-10.0004 V
0 mA
:
:
-11.7589 V
0 mA
0 V
0 mA
Ä Chapter 2.6.1 "System data AC500" on page 971 are
Ä Chapter 2.7.1 "System data AC500-XC" on page 1023 are
3ADR010278, 3, en_US
Ni1000
Digital value
-50...150 °C
Decimal
-50.1 °C
-501
:
:
-60.0 °C
-600
< -60.0 °C
-32768
4...20 mA
Digital value
Decimal
0 mA
> 32511
22.8142 mA
32511
:
:
20.0006 mA
27649
20.0000 mA
27648
:
:
4.0006 mA
1
4.0000 mA
0
3.9994 mA
-1
0 mA
-6912
0 mA
-27648
0 mA
-27649
:
:
0 mA
-32512
0 mA
< -32512
Hex.
FE0B
:
FDA8
8000
Hex.
> 7EFF
7EFF
:
6C01
6C00
:
0001
0000
FFFF
E500
9400
93FF
:
8100
< 8100