Device specifications
Communication interface modules (S500) > CANopen
Bus length
The maximum possible bus length of a CAN network depends on bit rate (transmission rate)
and cable type. The sum of all bus segments must not exceed the maximum bus length
Bit Rate (speed)
1 Mbit/s
800 kbit/s
500 kbit/s
250 kbit/s
125 kbit/s
50 kbit/s
Connection of the digital inputs
The following figure shows the connection of the digital input DI8. Proceed with the digital inputs
DI9 to DI15 in the same way.
Fig. 117: Connection of the digital inputs to the module CI582-CN
Connection of the digital outputs
The following figure shows the connection of the digital output DO8. Proceed with the digital
outputs DO9 - DO15 in the same way.
666
Bus Length
40 m
50 m
100 m
250 m
500 m
1000 m
+
24 V DC
-
3ADR010278, 3, en_US
3.0
DI8
3.1
DI9
3.2
DI10
3.3
DI11
3.4
DI12
3.5
DI13
3.6
DI14
3.7
DI15
3.8
UP
3.9
ZP