Device specifications
I/O modules > Analog I/O modules
3
)
4
)
State LEDs
During the power ON procedure, the module initializes automatically. All LEDs (except the
channel LEDs) are ON during this time.
LED
Measuring ranges
Input ranges of voltage, current and digital input
The represented resolution corresponds to 16 bits.
Range
Overflow
Measured
value too
high
Normal
range
Normal
range or
measured
value too
low
426
With "Module" the following allocation applies depending on the master:
Module error: I/O bus or FBP: 31 = module itself; COM1/COM2: 1...10 = expan-
sion 1...10
Channel error: I/O bus or FBP = module type (1 = AI, 3 = AO); COM1/COM2:
1...10 = expansion 1...10
In case of module errors, with channel "31 = Module itself" is output.
State
Inputs/
Analog input/
outputs
output
00...07
UP
Process
voltage
24 V DC via
terminal
CH-ERR3
Channel
error, error
messages
combined
into group 3
0...10 V
-10...+10
V
>11.7589
>11.7589
11.7589
11.7589
:
:
10.0004
10.0004
10.0000
10.0000
:
:
0.0004
0.0004
0.0000
0.0000
3ADR010278, 3, en_US
Color
LED = OFF
Yellow Input/output
is OFF
Green Process
voltage is
missing
Red
No error or
process
voltage is
missing
0...20 mA 4...20 mA Digital
>23.5178
>22.8142
23.5178
22.8142
:
:
20.0007
20.0006
20.0000
20.0000
:
:
0.0007
4.0006
0
4
LED = ON
LED flashes
Input/output is
--
ON (bright-
ness depends
on the value
of the analog
signal)
Process
--
voltage OK
Severe error
Error on one
within the cor-
channel of the
responding
group
group
Digital value
input
Decimal
32767
32511
:
27649
ON
27648
:
1
OFF
0
Hex.
7FFF
7EFF
:
6C01
6C00
:
0001
0000
2022/01/31