Device specifications
Communication interface modules (S500) > CANopen
Name
Input 3, Channel
configuration
Input 3, Check
channel
Table 137: Channel configuration - Operating modes of the analog inputs
Internal Value
0 (default)
1
2
3
4
5
8
9
10
11
14
15
16
17
18
19
*) In the operating modes with 3-wire configuration or with differential inputs, two adjacent
analog inputs belong together (e.g. the channels 0 and 1). In these cases, both channels
are configured in the desired operating mode. The lower address must be the even address
(channel 0). The next higher address must be the odd address (channel 1). The converted
analog value is available at the higher address (channel 1).
Table 138: Channel monitoring
Internal Value
0 (default)
3
642
Value
Internal value
Operation modes
Operation modes
of analog inputs
of analog inputs
Settings channel
Settings channel
monitoring
monitoring
3ADR010278, 3, en_US
Internal value,
type
BYTE
BYTE
Operating Modes (individually configu-
rable)
Not used
0...10 V
Digital input
0...20 mA
4...20 mA
-10 V...+10 V
2-wire Pt100 -50...+400 °C
3-wire Pt100 -50...+400 °C *)
0...10 V (voltage diff.) *)
-10 V...+10 V (voltage diff.) *)
2-wire Pt100 -50...+70 °C
3-wire Pt100 -50...+70 °C *)
2-wire Pt1000 -50...+400 °C
3-wire Pt1000 -50...+400 °C *)
2-wire Ni1000 -50...+150 °C
3-wire Ni1000 -50...+150 °C *)
Check Channel
Plausib(ility), cut wire, short circuit
Not used
Default
0
0
2022/01/31