ABB AC500 V3 Hardware Manual page 391

Hide thumbs Also See for AC500 V3:
Table of Contents

Advertisement

Technical data of the analog outputs
Parameter
Number of channels per module
Distribution of channels into groups
Connection of the signals O0U- and O1U+
Connection of the signals O0I+ and O1I+
Output type
Resolution
Conversion error of the analog values
caused by non-linearity, adjustment error
at factory and resolution within the normal
range
Indication of the output signals
Output Resistance (load) as current output
Output load ability as voltage output
Output data length
Relationship between output signal and hex
code
Unused outputs
Overvoltage protection
Max. cable length (conductor cross section
> 0.14 mm²)
Unshielded wire
Shielded wire
Ordering data
Part no.
1TNE 968 902 R1201 AO561, analog output module, 2 AO,
1TNE 968 901 R3102 Terminal block TA563-11, 11 pins,
2022/01/31
NOTICE!
Attention:
All I/O channels (digital and analog) are protected against reverse polarity,
reverse supply, short circuit and continuous overvoltage up to 30 V DC.
Description
U/I
screw front, cable side, 6 pieces per
unit
3ADR010278, 3, en_US
I/O modules > Analog I/O modules
Value
2 configurable voltage or current outputs
1 (2 channels per group)
Terminals 13 and 15
Terminals 14 and 16
Bipolar with voltage, unipolar with current
12 bits or 11 bits plus sign
Typ.
±0.5 % of full scale
at 25 °C
Max.
±2 % of full scale
at 0 °C...+60 °C or EMC disturbances
No
0 W...500 W
±2 mA max.
4 bytes
Ä Chapter 1.6.2.1.4.8 "Output ranges"
on page 389
Must not be connected and must be configured
as "unused"
Yes, up to 30 V DC
10 m
100 m
Product life cycle phase *)
Active
Active
Device specifications
391

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ac500-eco v3Ac500-xc v3

Table of Contents