Device specifications
I/O modules > Digital I/O modules
Parameter
Way of operation
Max. output voltage at signal 1
Output delay
Output data length
Output current
Output type
Protection type
Rated protection fuse (for each channel)
Demagnetization when inductive loads are
switched off
Switching Frequencies
Short-circuit-proof / Overload-proof
Connection of 2 outputs in parallel
Max. cable length
Ordering data
Part no.
1TNE 968 902 R2301 DX561, digital input/output module,
1TNE 968 901 R3101 Terminal block TA563-9, 9 pins, screw
1TNE 968 901 R3102 Terminal block TA563-11, 11 pins,
1TNE 968 901 R3103 Terminal block TA564-9, 9 pins, screw
254
0 to 1
1 to 0
Rated current per channel (max.)
Rated current per group (max.)
Rated current (all channels together,
max.)
Lamp load (max.)
Max. leakage current with signal 0
With inductive loads
With lamp loads
Overload message
Output current limitation
Resistance to feedback against 24 V DC No
Shielded
Unshielded
Description
8 DI 24 V DC, 8 DO 24 V DC,
transistor output
front, cable side, 6 pieces per unit
screw front, cable side, 6 pieces per
unit
front, cable front, 6 pieces per unit
3ADR010278, 3, en_US
Value
Non-latching type
20 V DC at max. current consumption
50 µs
200 µs
1 byte
0.5 A at UP 24 V DC
4 A
4 A
5 W
0.5 mA
Non-protected
External fuse on each channel
3 A fast
Must be performed externally according to
driven load specification
Max. 0.5 Hz
Max. 11 Hz at max. 5 W
No
No
No
Not possible
500 m
150 m
Product life cycle phase *)
Active
Active
Active
Active
2022/01/31