5.15.11 Cabinet Load Connections – Single Phase Loads
Note
AC input, AC Load and sense wiring are NOT included with the power source Cabinet
and must be supplied by the end-user. Only internal cabinet wiring and terminal
blocks are included.
Note that the Neutral connection for single-phase loads will have to carry all the line current
so the wire size must be chosen accordingly. Since AFX cabinets come standard with a three-
phase output terminal block, the three output terminals A, B and C must be shorted
together, either at the load or at the output terminal block as shown in the diagram below.
Entire Contents Copyright
2018 by Pacific Power Source, Inc. (PPS) • All Rights Reserved • No reproduction without written authorization from PPS.
AFX Series Power Source Operation Manual

Figure 5-19: Single Phase Load Connection Diagram

AFX SERIES® OPERATION MANUAL
SECTION 5: UNPACKING AND INSTALLATION
L
N
Page 80 of 485