List Parameters; Table 6-7: Available List Transient Parameters - Pacific Power Source AFX Series Operation Manual

Programmable power source
Hide thumbs Also See for AFX Series:
Table of Contents

Advertisement

6.6.2

LIST Parameters

The following parameters are available in each list transient list step.
PARAMETER
#
Ramp
Frequency
Voltage AC
Voltage DC
Dwell
Entire Contents Copyright
2018 by Pacific Power Source, Inc. (PPS) • All Rights Reserved • No reproduction without written authorization from PPS.
AFX Series Power Source Operation Manual
Range
Unit
1 - 199
-
0.2 - 9999
msec.
16 – 1200
Hz
0 – 300
V rms
0 – 425
V dc
0.2 - 9999
msec.

Table 6-7: Available LIST Transient Parameters

AFX SERIES® OPERATION MANUAL
Front Panel Operation
SECTION 6:
Description
Displays the row number in the
transient table. These numbers are
generated automatically.
Ramp time to slew from existing set
point to new set point value. Applies
to both Frequency and Voltage.
If previous set value is the same as
new value, the value is not slewed
but rather stays at the same value for
the duration of the ramp time.
New frequency value
New AC voltage value
New DC voltage value
Dwell time. At the end of the ramp
time, the new set values remain in
effect during the dwell period. At the
end of the dwell time, the next list
entry (if any) will be executed.
Page 134 of 485

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents