Pacific Power Source AFX Series Operation Manual page 469

Programmable power source
Hide thumbs Also See for AFX Series:
Table of Contents

Advertisement

Error Source
Code
Inverter Fault
278
Inverter Fault
279
Inverter Fault
280
Inverter Fault
281
Inverter Fault
282
Inverter Fault
283
Inverter Fault
284
Inverter Fault
286
Inverter Fault
287
Inverter Fault
288
Inverter Fault
289
Inverter Fault
290
Inverter Fault
291
Inverter Fault
292
Inverter Fault
293
Entire Contents Copyright
2018 by Pacific Power Source, Inc. (PPS) • All Rights Reserved • No reproduction without written authorization from PPS.
AFX Series Power Source Operation Manual
Category
Error Message
Error
Temperature protection
Error
Output relay voltage
protection
Error
Output relay voltage
protection
Error
Output terminals
common mode voltage
protection
Error
Output terminals
common mode voltage
protection
Error
Inductor current RMS
protection
Error
Inductor current DC
protection
Error
Fan under voltage
protection.
Error
Inductor current cycle-by-
cycle protection trip limit.
Error
Fan current consumption
is abnormal
Error
Hardware revision does
not match expected by
firmware. Firmware must
be reloaded.
Error
Invalid node ID. Run unit
discovery to recover.
Error
Incorrect DSP type
detected. Cycle-power to
re-try.
Error
Output current has too
much high frequency
content
Error
Controller missed
heartbeats from master
front panel.
AFX SERIES® OPERATION MANUAL
Service and Maintenance
SECTION 13:
Possible Cause
heatsink temperature
exceeds maximum limit.
Over Temperature.
Output inverter stage
heatsink temperature
exceeds minimum limit.
Overload condition.
Output relay voltage
minimum limit.
Overload condition.
Output relay voltage
maximum limit.
Overload condition.
Common mode voltage
below minimum limit
Overload condition.
Common mode voltage
above maximum limit
Overload condition.
Output Filter Inductor AC
current levels exceeded
maximum limit for too
long
Overload condition.
Output Filter Inductor DC
current levels exceeded
maximum limit for too
long
Fan Related Issue. Fan
voltage too low
Overload condition.
Output frequency
components too high for
output inductor
Fan Related Issue. Fan
may be blocked
Firmware Error. Firmware
revision mismatch
between front panel and
power stages
An inconsistency was
detected in the power
source's internal
communication network.
Internal Communication
Error. Incorrect DSP type
reported
Overload condition.
Possible oscillation. RQ
monitor fault.
Power stage has lost
communication with
front panel controller.
Front panel processor
may have locked up
Resolution
Check load levels or
ambient temperature
Possible inductive kick
back from Load
Possible inductive kick
back from Load
Reduce frequency,
voltage or load
Reduce frequency,
voltage or load
Contact customer service
Reduce frequency,
voltage or load
Contact customer service
Check for correct
firmware image file and
version.
Turn unit off, check
parallel cables if they
exist, and then turn unit
on. If problem recurs
contact customer service.
Try recycling power. If
error persists, contact
customer service
Reduce frequency,
voltage or load
Contact customer service