Pacific Power Source AFX Series Operation Manual page 333

Programmable power source
Hide thumbs Also See for AFX Series:
Table of Contents

Advertisement

Command Syntax
Description
Parameters
Parameter Format
Example
Query Format
Description
Returned Data Format
Query Example
Command Syntax
Description
Parameters
Parameter Format
Example
Query Format
Description
Returned Data Format
Query Example
Query Format
Description
Returned Data Format
Query Example
Query Format
Description
Returned Data Format
Query Example
Entire Contents Copyright
2018 by Pacific Power Source, Inc. (PPS) • All Rights Reserved • No reproduction without written authorization from PPS.
AFX Series Power Source Operation Manual
[SOURce:]INTHarmonic:VOLTage[:AC#]
Sets the inter harmonic voltage amplitude for the selected phase (1 =
A, 2 = B, 3 = C) or for all three phases if the phase selection is omitted
in Vac RMS
Voltage
<nr2>
INTH:VOLT:AC1 12.00
[SOURce:]INTHarmonic:VOLTage[:AC#]?
Query format returns the interharmonic amplitude setting.
<nr2>
INTH:VOLT?
12.0000, 0.0000, 0.0000
[SOURce:]INTHarmonic:VOLTage:AC#:DEFault
Sets the default amplitude of the interharmonic voltage component
for all phases. The factory default setting is 0.000 Vrms.
Frequency
<nr2>
INTH:VOLT:AC:DEF 5
[SOURce:]INTHarmonic:VOLTage:AC#:DEFault?
Query format returns the interharmonic default amplitude setting.
<nr2>
INTH:VOLT:AC:DEF?
5.0000, 5.0000, 5.0000
[SOURce:]INTHarmonic:VOLTage:AC#:MAXimum?
Returns the maximum value for the interharmonic amplitude setting
which is 300.0000 Vac RMS.
<nr2>
INTH:VOLT:AC:MAX?
300.0000
[SOURce:]INTHarmonic:VOLTage:AC#:MINimum?
Returns the minimum value for the interharmonic amplitude setting
which is 0.0000 Vac RMS.
<nr2>
INTH:VOLT:AC:MIN?
0.0000
AFX SERIES® OPERATION MANUAL
Remote Control Programming
SECTION 8:
Page 333 of 485

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents