AFX Series Power Source Operation Manual
[SOURce:]CURRent:LIMit#:MAXimum?
This command returns the maximum current limit setting available
for the referenced phase.
<nr2>
CURR:LIM:MAX1?
41.67
[SOURce:]CURRent:LIMit#:MINimum?
This command returns the minimum current limit setting available for
the referenced phase.
<nr2>
CURR:LIM:MIN1?
0.000
[SOURce:]CURRent:LIMit:AUTO
This commands enables or disables the Auto Current Limit function.
This function automatically adjusts the programmed current limit
level as a function of programmed voltage along the constant power
curve of the voltage range.
For example: On a 3150AFX model in three phase mode, if VOLT = 0
and CURR:LIM = 41.67 and voltage is changed to V = 300, the
CURR:LIM will change to: 5000 VA / 300 Vac = 16.0.
If CURR:LIM:AUTO = OFF then the CURR:LIM setting will remain at
41.67A and the power source will power limit at 5000VA instead if
the load draws more than 16Aac.
< 0 | OFF | 1 | ON >
<b>
CURR:LIM:AUTO ON
[SOURce:]CURRent:LIMit:AUTO?
<b>
CURR:LIM:AUTO?
1
[SOURce:]CURRent:OVerload
This command turns the overload current mode on or off
[ 0 | OFF | 1 | ON ]
<b>
SOUR:CURR:OV ON
[SOURce:]CURRent:OVerload?
<b>
CURR:OV?
1
AFX SERIES® OPERATION MANUAL
Remote Control Programming
SECTION 8:
Page 275 of 485