Query Format
Description
Returned Data Format
Query Example
Query Format
Description
Returned Data Format
Query Example
8.4.4

Power Measurement Commands

Query Format
Description
Returned Data Format
Query Example
Query Format
Description
Returned Data Format
Query Example
Query Format
Description
Returned Data Format
Query Example
8.4.5

KWh Measurement Commands

Query Format
Description
Returned Data Format
Query Example
Entire Contents Copyright
2018 by Pacific Power Source, Inc. (PPS) • All Rights Reserved • No reproduction without written authorization from PPS.
AFX Series Power Source Operation Manual
MEASure:CURRent:DC#?
Returns the measured DC current for the selected phase #. If no
phase number is specified, returns the reading for all phases.
<nr2>
MEAS:CURR:DC1?
0.0000
MEASure:CURRent:AC#?"
Returns the measured RMS current for the selected phase #. If no
phase number is specified, returns the reading for all phases. This
command is equivalent to "MEASure:CURRent[:ACDC]#?" and is
provided for backward compatibility with the UPC controllers.
<nr2>
MEAS:CURR:AC1?
21.1587
MEASure:POWer#?
Returns the true power for the selected phase # in kW. If no phase
number is specified, returns the reading for all phases.
<nr2>
MEAS:POWer1?
4.4203
MEASure:KVA#?
Returns the true apparent for the selected phase # in kVA. If no
phase number is specified, returns the reading for all phases.
<nr2>
MEAS:KVA1?
4.8665
MEASure:PF#?
Returns the true apparent for the selected phase # in kVA. If no
phase number is specified, returns the reading for all phases.
<nr2>
MEAS:PF1?
0.9083
MEASure:KWHour#?
Returns the accumulated energy measurement for the selected
phase # in kWh. If no phase number is specified, returns the total
summed KWh for all phases.
<nr2>
MEASure:KWHour?
12.4203
AFX SERIES® OPERATION MANUAL