Ethernet/Ip: Configuration Error; Cavitation Protection Failure; Cavitation Protection Warning - Siemens SINAMICS G120X Operating Instructions Manual

Infrastructure converter for hvac/water/wastewater
Hide thumbs Also See for SINAMICS G120X:
Table of Contents

Advertisement

Acknowledge:
POWER ON
Cause:
An internal software error has occurred.
Fault value (r0949, interpret decimal):
Information about the fault source.
Only for internal Siemens troubleshooting.
Remedy:
- if necessary, upgrade the firmware in the Terminal Module to a later version.
- contact Technical Support.
A50010 (F)
PROFINET: Consistency error affecting adjustable parameters
Reaction:
NONE
Acknowledge:
NONE
Cause:
A consistency error was detected when activating the configuration (p8925) for the PROFINET interface. The currently set
configuration has not been activated.
Alarm value (r2124, interpret decimal):
0: general consistency error
1: error in the IP configuration (IP address, subnet mask or standard gateway).
2: Error in the station names.
3: DHCP was not able to be activated, as a cyclic PROFINET connection already exists.
4: a cyclic PROFINET connection is not possible as DHCP is activated.
Note:
DHCP: Dynamic Host Configuration Protocol
See also: p8920 (PN Name of Station), p8921 (PN IP address), p8922 (PN Default Gateway), p8923 (PN Subnet Mask),
p8924 (PN DHCP Mode)
Remedy:
- check the required interface configuration (p8920 and following), correct if necessary, and activate (p8925).
or
- reconfigure the station via the "Edit Ethernet node" screen form (e.g. with STARTER commissioning software).
See also: p8925 (Activate PN interface configuration)
A50011 (F)

Ethernet/IP: configuration error

Reaction:
NONE
Acknowledge:
NONE
Cause:
An EtherNet/IP controller attempts to establish a connection using an incorrect configuring telegram.
The telegram length set in the controller does not match the parameterization in the drive device.
Remedy:
Check the set telegram length.
For p0922 not equal to 999, then the length of the selected telegram applies.
For p0922 = 999, the maximum interconnected PZD (r2067) applies.
See also: p0922, r2067
F52960

Cavitation protection failure

Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
Conditions exist for cavitation damage. Cavitation damage is damage caused to a pump in pumping systems when the fluid
is not flowing sufficiently. This can lead to heat build up and subsequent damage to the pump.
Remedy:
If cavitation is not occurring, reduce the cavitation threshold p29626, or increase the cavitation protection delay. Ensure
sensor feedback is working.
A52961

Cavitation protection warning

Reaction:
NONE
Acknowledge:
NONE
Cause:
Conditions for possible cavitation damage are detected.
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Warnings, faults and system messages
9.6 List of fault codes and alarm codes
1047