Writing an application configuration to the IED

The application configuration is created using PCM600 and then written to the IED. Establish a
connection between PCM600 and the IED when an application configuration must be written
to the IED.
After writing an application configuration to the IED, the IED makes an application restart or a
complete IED restart, when necessary.
30
Select: Use the following IP address
The PC and IED must belong to the same subnetwork for this set-up to work.
Ensure that the IED includes the correct application configuration according to
project specifications.
The IED does not restart after reconfiguring IEC61850 (regardless of whether
the protocol is enabled or disabled).
Be sure to set the correct technical key in both the IED and PCM600 to prevent
writing an application configuration to a wrong IED.