Autorecloser (AR)

Autorecloser counter values

Table 149: Autorecloser counter values AR (AR---)
Viewed data (default labels used, data is exam-
ple values)
3ph-Shot1=
nnn
3ph-Shot2=
nnn
3ph-Shot3=
nnn
3ph-Shot4=
nnn
NoOfReclosings=
nnn

Setting parameters

Path in local HMI: Settings/Functions/Group1/Autorecloser/Autorecloser1
Table 150: Setting parameters for the automatic reclosing AR (AR---) function
Parameter
Range
Operation
Off,
Stand-by,
On
NoOfReclosing
1-4
Extended t1
Off, On
t1
0.000-60.000
Step: 0.001
t2
0.0-90000.0
Step: 0.1
t3
0.0-90000.0
Step: 0.1
t4
0.0-90000.0
Step: 0.1
tSync
0.0-90000.0
Step: 0.1
tPulse
0.000-60.000
Step: 0.001
CutPulse
Off, On
tReclaim
0.0-90000.0
Step: 0.1
tInhibit
0.000-60.000
Step: 0.001
Counter value
Recorded number of first three-pole reclosing
attempts
Recorded number of second three-pole reclosing
attempts
Recorded number of third three-pole reclosing
attempts
Recorded number of fourth three-pole reclosing
attempts
Recorded number of all reclosing attempts
Default
Unit
Description
Off
-
Operating mode for AR function
1
-
Maximum number of reclosing attempts
Off
-
Extended dead time for loss of permis-
sive channel
1.000
s
Dead time for first three-phase automatic
reclosing shot
30.0
s
Dead time for second automatic reclosing
shot
30.0
s
Dead time for third automatic reclosing
shot
30.0
s
Dead time for fourth automatic reclosing
shot
2.0
s
Maximum wait time for sync
0.200
s
Circuit breaker closing pulse length
Off
-
Shorten closing pulse at a new trip
60.0
s
Reclaim time
5.000
s
Inhibit reset time