Earthing (Grounding) Precautions - Mitsubishi Electric 800 Series Instruction Manual

Connection
Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

NOTE
• Especially for long-distance wiring, the inverter may be affected by a charging current caused by stray capacitances of the
wiring, leading to an activation of the overcurrent protection, malfunction of the fast-response current limit operation, or even
to an inverter failure. It may also cause a malfunction or fault of the equipment connected ON the inverter output side. If the
fast-response current limit function malfunctions, disable the function. (Refer to Pr.156 Stall prevention operation selection
in the FR-E800 Instruction Manual (Function).)
• A surge voltage suppression filter (FR-ASF-H/FR-BMF-H) can be used under V/F control and Advanced magnetic flux vector
control.
• For the details of Pr.72 PWM frequency selection, refer to the FR-E800 Instruction Manual (Function).
• Refer to
page 102
• The carrier frequency is limited during Real sensorless vector control and PM sensorless vector control. (Refer to the FR-E800
Instruction Manual (Function).)
2.5.4

Earthing (grounding) precautions

Always earth (ground) the motor and inverter.
 Purpose of earthing (grounding)
Generally, an electrical apparatus has an earth (ground) terminal, which must be connected to the ground before use.
An electrical circuit is usually insulated by an insulating material and encased. However, it is impossible to manufacture an
insulating material that can shut off a leakage current completely, and actually, a slight current flows into the case. The purpose
of earthing (grounding) the case of an electrical apparatus is to prevent operators from getting an electric shock from this
leakage current when touching it.
To avoid the influence of external noises, the earthing (grounding) is important to EMI-sensitive equipment that handle low-
level signals or operate very fast such as audio equipment, sensors, and computers.
 Earthing (grounding) system to be established
As described previously, the purpose of earthing (grounding) is roughly classified into the electrical shock prevention and the
prevention of malfunction due to the influence of electromagnetic noise. These two purposes should be clearly distinguished,
and the appropriate earth (ground) system must be established to prevent the leakage current having the inverter's high
frequency components from reversing through another earth (ground) point for malfunction prevention by following these
instructions:
• Make the separate earth (ground) connection (I) for high frequency products such as the inverter from any other devices
(EMI-sensitive devices described above) wherever possible.
Establishing adequate common (single-point) earth (ground) system (II) shown in the following figure is allowed only in
cases where the separate earth (ground) system (I) is not feasible. Do not make inadequate common (single-point) earth
(ground) connection (III).
As leakage currents containing many high frequency components flows into the earthing (grounding) cables of the inverter
and peripheral devices (including a motor), the inverter must also be earthed (grounded) separately from EMI-sensitive
devices described above.
In a high building, it may be effective to use its iron structure frames as earthing (grounding) electrode for EMI prevention
in order to separate from the earth (ground) system for electric shock prevention.
- Earthing (Grounding) must conform to the requirements of national and local safety regulations and electrical codes
(NEC section 250, IEC 61140 class 1 and other applicable standards). A neutral-point earthed (grounded) power supply
for 400 V class inverter in compliance with EN standard must be used.
- Use the thickest possible earthing (grounding) cable. The earthing (grounding) cable should be the size indicated in the
table on
page
47.
- The earthing (grounding) point should be as close as possible to the inverter, and the earth (ground) wire length should
be as short as possible.
- Run the earthing (grounding) cable as far away as possible from the I/O wiring of the EMI-sensitive devices and run
them in parallel in the minimum distance.
to drive a 400 V class motor by an inverter.
10
51
2. Installation and Wiring
2.5 Main circuit terminals
1
2
3
4
5
6
7
8
9

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents