High−level Instructions
For FP−X Tr type
Channel no.
Output
ch0
Y0
Y1
ch1
Y2
Y3
ch2
Y4
Y5
ch3
Y6
Y7
Note) There is no ch3 for C14T and C14TD.
Note) The pulse I/O cassette (AFPX−PLS) cannot be installed on the FP−X Tr type.
Note) Use the ch2 and ch3 at up to 20 kHz.
When the elapsed value of the high−speed counter reaches the target value specified in the data table, the
pulse frequency is switched (interrupt processing is carried out).
When the elapsed value agrees with the last target value, the pulse output operation finishes.
Use the F0 (MV) instruction to control the high−speed counter to force the pulse output control to stop.
If the frequency is set to 50 kHz or more, specify a duty of 1/4 (25%).
If the frequency for ch2 or ch3 of FP−X Tr type is set to 10kHz or more, specify a duty of 1/4 (25%).
Table of areas used
For FPΣ
Channel no.
Control flag
ch0
R903A
ch2
R903C
For FP−X Ry type
Channel no.
Control flag
ch0
R911C
ch1
R911D
For FP−X Tr type
Channel no.
Control flag
ch0
ch0
R911C
R911C
ch1
ch1
R911D
R911D
ch2
ch2
R911E
R911E
ch3
ch3
R911F
R911F
Note) There is no ch3 for C14T and C14TD.
Note) The pulse I/O cassette (AFPX−PLS) cannot be installed on the FP−X Tr type.
Note) Use the ch2 and ch3 at up to 20 kHz.
3 − 534
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Output method
CW
PLS
CCW
SIGN
CW
PLS
CCW
SIGN
CW
PLS
CCW
SIGN
CW
PLS
CCW
SIGN
Elapsed value area
Target value area
DT90044, DT90045
DT90046, DT90047
DT90200, DT90201
DT90202, DT90203
Elapsed value area
Target value area
DT90348, DT90349
DT90350, DT90351
DT90352, DT90353
DT90354, DT90355
Elapsed value area
Target value area
DT90348
DT90349
DT90352
DT90353
DT90356
DT90357
DT90360
DT90361
DT90350
DT90351
DT90354
DT90355
DT90358
DT90359
DT90362
DT90363
FPΣ/FP−X