Specifications for each item
The control data specified by [S1][S1+1] is specified as follows.
[S1]: Specifying transmission unit and transmission method
H0
[S1]:
Word unit
Specifies No. of transmisson words
transmission
H001 to H1FD (1 to 509 words): when transmitting to Group A
H001 to H1B (1 to 27 words): when transmitting to Group B
Group A
Group B
H8
[S1]:
Bit No. of local
Bit unit
unit (H0 to HF)
transmission
[S1+1]: Specifying the remote unit
H0 fixed
[S1+1]:
Selects COM port
(H1 or H2)
(1) Specifying the transmission unit and transmission method [S1]
If data is to be sent in word units, specify the data volume, and if it is to be sent in bit units, specify the position of the
target bit.
(2) Specifying the remote unit [S1+1]
Specify the remote unit with the unit number.
Specify either the COM1 or COM2 port from which data is transmitted to the remote unit.
Specify H1 if only one COM port is available.
(3) Specifying the area of the remote unit which is received by [S2] and [N].
Specify 0 for the device No. of [S2].
Specify the memory area of the remote unit in which the data to be transmitted is stored, specifying the type S2 and
the address N in combination.
Example)
[S2]:DT0, [N]:K100
DT100
For the FP0R, FPΣ V3.20 or later, FP−X V2.50 or later, transmission can be performed without checking when DT0 or
LD0 is specified for D, and H constant is specified for N.
(Example) In case of DT0 and HFFFF, it is possible to access DT63353. It is convenient to access the data registers
of an eco−power meter KW8M.
(4) Specifying the area of the local unit by [D] in which the data to be received is stored
Specify the memory area of the local unit in which the data to be received is stored.
The MEWTOCOL−COM command is created according to the operands specified by [S1],[S1+1], [S2],
[D], and [N].
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
FPΣ, FP−X, FP0R, FP2,
FP2SH, FP10SH
FP0, FP−e
H0 fixed
Bit No. of remote
unit (H0 to HF)
Unit No. (H01 to H63)
(1 to 99)
High−level Instructions
3 − 361