5.1.17 Table of Special Internal Relays for FP1/FP-M/FP2/FP2SH/FP10SH/FP3

FP1/FP-M/FP2/FP2SH/FP10SH/FP3
Address
Self-diagnostic error
flag
R9000
(Available PLC: All
types)
R9001
Not used
MEWNET-TR master
error flag
(Available PLC: FP3/
FP10SH)
R9002
I/O error flag
(Available PLC: FP2/
FP2SH)
Intelligent unit error
R9003
flag
I/O verification error
R9004
flag
Backup battery error
flag (non-hold)
(Available PLC: FP-M
R9005
C20, C32/FP1 C24,
C40, C56, C72/FP2/
FP2SH/FP3/FP10SH)
Backup battery error
flag (hold)
(Available PLC: FP-M
R9006
C20, C32/FP1 C24,
C40, C56, C72/FP2/
FP2SH/FP3/FP10SH)
Operation error flag
R9007
(hold)
Operation error flag
(non-hold)
R9008
(Available PLC:
FP1/FP-M/FP2/FP2SH/
FP10SH)
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Name
Turns on when a self-diagnostic error occurs.
The self-diagnostic error code is stored in:
- FP1/FP-M/FP3: DT9000
- FP2/FP2SH/FP10SH: DT90000
-
Turns on when a communication error occurs in the
MEWNET-TR master unit or MEWNET-TR network. The
slot, where the erroneous MEWNET-TR master unit is
installed, can be checked using:
- FP3: DT9002 and DT9003
- FP10SH: DT90002, DT90003
Turns on when the error occurs in the I/O unit. The slot
number of the unit where the error was occurred is stored in
DT90002, DT90003.
Turns on when an error occurs in an intelligent unit. The slot
number, where the erroneous intelligent unit is installed is
stored in:
- FP3: DT9006 and DT9007
- FP2/FP2SH/FP10SH: DT90006, DT90007
Turns on when an I/O verification error occurs.
The slot number of the I/O unit where the verification error
was occurred is stored in:
- FP3: DT9010 and DT9011
-FP2/FP2SH/FP10SH: DT90010, DT90011
Turns on for an instant when a backup battery error occurs.
Turns on and keeps the on state when a backup battery
error occurs. To reset R9006,
- turn the power to off and then turn it on,
- initialize, after removing the cause of error.
Turns on and keeps the on state when an operation error
occurs. The address where the error occurred is stored in:
- FP1/FP-M/FP3: DT9017
– FP2/FP2SH/FP10SH: DT90017
(Indicates the first operation error which occurred).
Turns on for an instant when an operation error occurs. The
address where the operation error occurred is stored in:
- FP1/FP-M/FP3: DT9018
-FP2/FP2SH/FP10SH: DT90018
The contents change each time a new error occurs.
Description