No.
402
Inter-
rupt-
input
403
Note1) If the operation mode is set to Two-phase, incremental/decremental, or incremental/decremental
control, the setting for CH1 is invalid in part 2 of system register 400 and the setting for CH3 is
invalid in part2 of system register 401.
Note2) If reset input settings overlap, the CH1 setting takes precedence in system register 400 and the
CH3 setting takes precedence in system register 401.
Note3) The settings for pulse catch and interrupt input can only be specified in system registers 402 and
403.
Note4) If system register 400 to 403 have been set simultaneously for the same input relay,the follwing
precedence order is effective: [High-speed counter]→[Pulse catch]→[Interrupt input].
<Example>
When the high-speed counter is being used in the addition input mode, even if input X0 is
specified as an interrupt input or as pulse catch input, those settings are invalid, and X0
functions as counter input for the high-speed counter.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Name
Pulse catch input
settings
Interrupt input
settings
Default
value
Not set
Specify the input contacts used as pulse catch
input.
Specify the input contacts used as intrrupt
input.
Not set
Specify the effective interrupt edge.
(When set: ON→OFF is valid)
Descriptions
5-81