Panasonic FP-E Programming Manual page 595

Fp series
Table of Contents

Advertisement

FP2/FP2SH/FP10SH
Preparation of reception
1) Setting the transmission format
For FP10SH
The initial settings for the transmission format are as follows:
− Data length: 8 bits
− Parity check: Yes, odd
− Stop bits: 1 bit
− End code: C
R
− Start code: No STX
To change the transmission format to match the external device connected to the COM. port, set the
parameters with the upper row of operation mode switches.
Operation mode switches (using upper dip switch)
off
on
off
on
Functions
MODEM
Disabled
control
t l
Enabled
Start code
STX (H02)
invalid
STX (H02) valid
End code
None
C
(H0D) and LF
R
(H0A)
C
(H0D)
R
EXT (H03)
Stop bit
p
2 bits
1 bit
Parity check
y
Invalid
Even parity
Odd parity
Data length
7 bits
(character
(character
8 bits
bit)
For FP2/FP2SH
Set the transmission format parameter so that the "Transmission Format Setting" of system register 413
matches the external device connected to the COM. port. The default setting is the same as that of the
FP10SH.
When the start code is vaild, the data from the reception of STX to the reception of the selected end code is
considered to be one frame.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Upper dip switches
Lower dip switches
Settings
SW1
SW2
SW3
off
on
off
on
off
on
off
on
High−level Instructions
SW4
SW5
SW6
off
off
on
on
off
on
off
on
on
SW7
SW8
off
off
on
off
on
3 − 331

Hide quick links: