Panasonic FP-E Programming Manual page 561

Fp series
Table of Contents

Advertisement

Description
Checks the state [on (1) or off (0)] of bit position specified by n in the 16-bit data specified by D. The judgment
result is output to special internal relay R900B (=flag).
The specified bit is checked by special internal relay R900B.
− When the specified bit is on (1), special internal relay R900B (= flag) turns off.
− When the specified bit is off (0), special internal relay R900B (= flag) turns on.
The "n" is decimal data specifying the bit position to be checked. Range of "n": K0 to K15
15
12 11
Bit position
· · ·
n
— — — — — — — —
The data in bit positions
4 through 15 are invalid.
Precaution when the judgement flag R900B is used two or more times
The judgment flag R900B is updated each time an operation instruction or comparison instruction is
executed.
If the judgment flag is used two or more times,
− the program in which the judgment flag is used should be input immediately following the instruction
which executes the judgment.
− the flag should be output to output relays or internal relays for each separate instruction.
Flag conditions
・Error flag (R9007):
・Error flag (R9008):
・= flag (R900B):
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
8 7
4 3
0
·
·
· ·
· ·
— — — —
0 0 0 0
Range of "n": K0 to K15 (H0 to HF)
Turns on and stays on when the area specified using the index modifier
exceeds the limit.
Turns on for an instant when the area specified using the index modifier
exceeds the limit.
Turns on for an instant when the specified bit to be checked is in the off (0)
state.
High−level Instructions
3 − 297

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fp0Fp2Fp2shFp0rFrsFp10sh ... Show all

Table of Contents