Panasonic FP-E Programming Manual page 763

Fp series
Table of Contents

Advertisement

FPΣ/FP−X
For FP−X Tr type
Channel no.
Output
ch0
Y4 or Y8
ch1
Y5 or Y9
ch2
ch3
Note) There is no ch3 for C14T and C14TD.
Note) C14T and C14TD is Y4 or Y5. C30T, C30TD, C60T and C60TD is Y8 or Y9.
Note) The deviation counter clear control is not available for the ch2 and ch3.
Note) Use the ch2 and ch3 at up to 20 kHz.
The control code, initial speed, maximum speed, acceleration/deceleration time, and deviation counter clear
signal are specified by creating a data table as described on the following page using the user program.
The frequency is changed using the specified acceleration/deceleration time from the initial speed to the
maximum speed. During deceleration, the frequency is changed based on the same slope as during
acceleration.
If the frequency is set to 50 kHz or more, specify a duty of 1/4 (25%).
If the frequency for ch2 or ch3 of FP−X Tr type is set to 10kHz or more, specify a duty of 1/4 (25%).
Table of areas used
For FPΣ
Channel no.
Control flag
ch0
R903A
ch2
R903C
For FP−X Ry type
Channel no.
Control flag
ch0
R911C
ch1
R911D
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Output method
Y0
CW
Y1
CCW
Deviation counter clear
Y2
CW
Y3
CCW
Deviation counter clear
Y4
CW
Y5
CCW
No deviation counter clear control
Y6
CW
Y7
CCW
No deviation counter clear control
Elapsed value area
DT90044, DT90045
DT90200, DT90201
Elapsed value area
DT90348, DT90349
DT90352, DT90353
PLS
SIGN
PLS
SIGN
PLS
SIGN
PLS
SIGN
Target value area
Near home
DT90046, DT90047
DT90052 bit2
DT90202, DT90203
DT90052 bit4
Target value area
Near home
DT90350, DT90351
DT90052 bit4
DT90354, DT90355
DT90052 bit4
High−level Instructions
Home input
X2
X5
Home input
X4
X5
3 − 499