Description
Performs exclusive NOR operation on each bit in the 16-bit equivalent constant or 16-bit data specified by S1
and S2. The exclusive NOR operation result is stored in the 16-bit area specified by D.
{(S1)
{(S1)
(S2)}
Detects the bits whose on and off states match.
If the values of S1 and S2 are equal, all the bits of the data specified by D become 1.
Exclusive NOR operation
The exclusive NOR operation is shown below.
S1
S2
D
0
0
1
0
1
0
1
0
0
1
1
1
Flag conditions
・Error flag (R9007):
・Error flag (R9008):
・= flag (R900B):