Panasonic FP-E Programming Manual page 727

Fp series
Table of Contents

Advertisement

FP0/FP−e/FPΣ/FP−X
Flag conditions
・Error flag (R9007):
・Error flag (R9008):
FP0, FP−e
Channel No.
ch0
ch1
ch2
ch3
FPΣ
Channel No.
ch0
ch1
ch2
ch3
FP−X Ry type:ch0 to chB
Channel No.
ch0
ch1
ch2
ch3
ch4
ch5
ch6
ch7
ch8
ch9
chA
chB
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Turns on and stays on when:
Turns on for an instant when:
− The area is exceeded when an index modifier is used.
− The "n" is outside specification range.
− The "S" is outside specification range.
− The "D" is outside specification range.
− The high−speed counter has not been set for the specified channel by the
system register.
Control flag
R903A
R903B
R903C
R903D
Control flag
R903A
R903B
R903C
R903D
T type : ch0 to ch7 FP0R: ch0 to ch5
Control flag
R9110
R9111
R9112
R9113
R9114
R9115
R9116
R9117
R9118
R9119
R911A
R911B
Elapsed value area
DT9044 to DT9045
DT9048 to DT9049
DT9104 to DT9105
DT9108 to DT9109
Elapsed value area
DT90044 to DT90045
DT90048 to DT90049
DT91200 to DT91201
DT91204 to DT91205
Elapsed value area
DT90300 to DT90301
DT90304 to DT90305
DT90308 to DT90309
DT90312 to DT90313
DT90316 to DT90317
DT90320 to DT90321
DT90324 to DT90325
DT90328 to DT90329
DT90332 to DT90333
DT90336 to DT90337
DT90340 to DT90341
DT90344 to DT90345
High−level Instructions
Target value area
DT9046 to DT9047
DT9050 to DT9051
DT9106 to DT9107
DT9110 to DT9111
Target value area
DT90046 to DT90047
DT90050 to DT90051
DT91202 to DT91203
DT91206 to DT91207
Target value area
DT90302 to DT90303
DT90306 to DT90307
DT90310 to DT90311
DT90314 to DT90315
DT90318 to DT90319
DT90322 to DT90323
DT90326 to DT90327
DT90330 to DT90331
DT90334 to DT90335
DT90338 to DT90339
DT90342 to DT90343
DT90346 to DT90347
3 − 463