High−level Instructions
If S2 specifies a higher word of real number data, processing will take place over the same area as if the lower
word had been specified.
Real number data table
Lower word
S1:
0
Higher word
S1+1:
S1+2:
1
S1+3:
Lower word
S2−1:
n
Higher word
S2:
Precautions during programming
Even if D+2 overflows the selected area, it will still be stored, and this may corrupt the data in the leading part
of the other area. (An area overflow check is not performed.)
Flag conditions
・Error flag (R9007):
・Error flag (R9008):
・Carry flag (R9009): Turns on for an instant when overflows/underflows while calculating.
3 − 756
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Specifies areas
Turns on and stays on when:
− The area specified using the index modifier exceeds the limit.
− S1 > S2.
− The areas of S1 and S2 are different.
− The real number data is outside possible operating range.
Turns on for an instant when:
− The area specified using the index modifier exceeds the limit.
− S1 > S2.
− The areas of S1 and S2 are different.
− The real number data is outside possible operating range.