Panasonic FP-E Programming Manual page 399

Fp series
Table of Contents

Advertisement

F62
(WIN)
P62
(PWIN)
Outline
Compares one 16-bit data item with the data band specified by two
other 16-bit data items and the comparison result is output to the
special internal relay.
For the FP0R/FPΣ/FP−X/FP0/FP−e, the P type high−level instruction
"P62 (PWIN)" is not available.
Program example
Trigger
R0
50
F62 WIN , DT10 , DT20 , DT 30
R0
R900A
58
R0
R900B
61
R0
R900C
64
S1
S2
S3
Operands
Relay
Operand
Operand
WX WY WR
A
A
S1
S2
A
A
S3
A
A
(*1) This cannot be used with the FP0 and FP−e.
(*2) This cannot be used with the FP0, FP−e, FP0R, FPΣ, FP−X.
(*3) With the FP0R, FPΣ, FP−X, FP2, FP2SH, and FP10SH, this is I0 to IC.
(*4) With the FP0R, FPΣ, FP−X, FP2, FP2SH, and FP10SH, this is ID.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
16-bit data band comparison
Ladder Diagram
Ladder Diagram
S1
S2
16-bit equivalent constant or 16-bit area to be compared
16-bit equivalent constant or 16-bit area for lower limit
16-bit equivalent constant or 16-bit area for upper limit
Timer/Counter
WL
SV
EV
DT
(*1)
A
A
A
A
A
A
A
A
A
A
A
A
Lower limit value
Upper limit value
S3
Y10
Y11
Y12
Index
Register
register
LD
FL
IX
IY
(*1)
(*2)
(*3)
(*4)
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
High−level Instructions
Boolean
Address
Instruction
50
ST
R
51
F 62
(WIN)
DT
DT
DT
58
ST
R
59
AN
R 900A
60
OT
Y
61
ST
R
62
AN
R 900B
63
OT
Y
64
ST
R
65
AN
R 900C
66
OT
Y
Constant
Index
Index
modifier
K
H
A
A
A
A
A
A
A
A
A
A:
Available
3 − 135
0
10
20
30
0
10
0
11
0
12

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fp0Fp2Fp2shFp0rFrsFp10sh ... Show all

Table of Contents