4.4.3
Dealing with Operation Errors
Procedure:
1. Check the location of the error.
Check the address where the error occurred, which is stored in DT9017
and DT9018 or in DT90017 and DT90018, and make sure the application
instruction for that address is correct and appropriate.
2. Clear the error.
Use a programming tool to clear the error. (If the mode selector is set to
RUN, RUN will resume as soon as the error is cleared.)
In the "STATUS DISPLAY" menu of the programming tool software
(NPST−GR Ver. 3.1 or later), press the "F3" key.
In FP Programmer II, press the following keys.
ACLR
An error can be cleared by turning the power off and on in PROG. mode,
however, the contents of the operation memory except the hold type data
will be cleared.
An error can also be cleared by executing the self-diagnostic error set
instruction F148 (ERR).