Panasonic FP-E Programming Manual page 1204

Fp series
Table of Contents

Advertisement

FP-X
Add-
Item
ress
410
Unit No. setting
Communication
mode setting
412
Selection of modem
connection
Communication
413
format setting
COM.
1
port
set-
ting
415
Baud rate setting
Starting address for
received buffer of
416
general (serial data)
communication mode
Buffer capacity
setting for data
417
received of general
(serial data)
communication mode
Note1) The communication format in a PC(PLC) link is fixed at the following settings:
Data length is 8 bits, odd parity, stop bit is 1.
The communication speed (baud rate) is fixed at 115200 bps.
Note2)
Reference: For information on MODBUS RTU mode operation, <MODBUS RUT
5-116
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Default
Name
value
1
Computer link
Disabled
Data length
bit: 8 bits
Parity check:
Odd
Stop bit: 1 bit
9600 bps
0
2048
Specifications>.
Description
1 to 99
Computer link
General-purpose serial communication
PC(PLC) link
MODBUS RTU
Enabled/Disabled
Enter the settings for the various items.
Data length bit: 7 bits/8 bits
-
Parity check: none/with odd/with even
-
Stop bit: 1 bit/2 bits
-
The following setting is valid only when
-
the communication mode specified by
system register 412 has been set to
"General-purpose serial communication".
Terminator: CR/CR+LF/None
-
Header: STX not exist/STX exist
-
2400 bps
4800 bps
9600 bps
19200 bps
38400 bps
57600 bps
115200 bps
0 to 32764
0 to 2048

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fp0Fp2Fp2shFp0rFrsFp10sh ... Show all

Table of Contents